FC-BRV-02-S rapid blast dampers are specifically developed for those applications where high air flow rate and blast protection are required. It could stand the overpressure up to 200KPa reflected with long duration and shut off in milliseconds. It could also stand multiple blast impacts and maintain full functions after blasts.
Able to stand multiple blast impacts and maintain all functions after blasts.
Approximate 100% blast impulse block rate to assure the sufficient protection.
Completely closed within 8ms under 200KPa peak pressure reflected and this assures the safety by minimizing
the passing through impulse.
High air flow based on normal open position. A 500*500 blast damper could provide exhaust air flow rate up
to 3800 m3/h at pressure differential 100Pa.
Designed peak pressure |
200KPa Reflected |
Designed blast duration |
20ms |
Closing time |
<8ms (200KPa reflected) |
Blast impulse block rate |
>98.5% (200KPa reflected) |
Operating temperature |
-30ºC to 285ºC |
ATEX Certification |
Certification No. TÜV 15 ATEX 7741 X Ⅱ2 G c ⅡC T6...T2 Ⅱ2 D c ⅢC T70℃...T285℃ |
ATO PN: FCBRV02S[A][B][C][D]
Code Options Descriptions A Material of damper 1-Stainless Steel 316L 2-Stainless Steel 304L 3-Hot galvanized steel 4-Epoxy coated steel B Mounting Type IW–In the wall OW–On wall surface D–Duct connected C Width (mm) 0300 0500 0700 1000 1200 1500 … D Height (mm) 0300 0500 0700 1000 1200 1500 …
(Non-ATEX)